www.powersolve.co.uk
Powersolve Electronics Ltd. 8A, Arnhem Road, Newbury, RG14 5RU. England
Specification
200 VA - 12 kVA
• Sinusoidal Output from 12-480 V
• Compact Switched Mode Design
• DC Inputs 10-400 V
• Wall or Rack Mounting
• Industrial Grade
• Customised Design Available
Inverter Series
Input
Input Voltage • See Table
No load Input Power • 20 W typical
Earth Leakage Current • <3.5 mA at 230 VAC
Output
Output Voltage • See Table
Output Voltage • 110 V version 110 V to 125 V
Adjustment 230 V version 210 V to 245 V
Minimum Load • No minimum load required
Wave Form • Sinusoidal standard, optional wave
shape programmable
by external signal
Frequency • Crystal stabilized 50 Hz, 60 Hz,
400 Hz or 45 to 400 Hz adjustable
Distortion • 3% typical (5% at 400 Hz)
Rise Time • 100 ms typical
Power Factor • Cos Ø≥0.7 inductive/capacitive
Crest Factor •3
Line Regulation • 0.1% for CI models,
2.0 % for I, IT & IV models
(±10% change Vin)
Load Regulation • 50/60 Hz 1% typical 3% max,
400 Hz 3% typical 5% max
(10-90% load change)
Overload • Current limited to approx 105%
Protection I Nom (Steady State)
Short Circuit • Electronically limited to 3 x I Nom
Current
Surge Power • 2 x P Nom for 1 sec
Temperature • 0.05%/°C typical
Coefficient
1
General
Efficiency • 85-95% I models,
75-90% CI, IT & IV models
Isolation • 3500 VDC Input to Output,
3500 VDC Input to Ground,
3500 VDC Output to Ground
Switching Frequency • Approx 33 kHz converter & 20 kHz
Inverter section
MTBF • 120,000 hours I & IT models,
70,000 hours CI models,
50,000 hours IV models
Dimensions/Weight • Contact Sales
Options • Contact Sales
Environmental
Operating Temperature • -20 °C to +75 °C, derate linearly at
2.5%/°C from +55 °C
Optional -40 °C to +75 °C
Storage Temperature • -40 °C to +85 °C
Cooling • Natural convection
(IT5600 to IT5800 forced cooled)
Operating Humidity • 5-95% RH non-condensing
Operating Altitude • 1000 m
EMC & Safety
Emissions • EN55022 Level A conducted,
optional Class B
EFT/Burst • EN61000-4-4 Level 3
Surge • EN61000-4-5 Level 3
Safety Approvals • EN60950
UPS/INVERTERS